These are mostly used for protection when protection with an MCCB is not possible, such as on low capacity control circuits, heaters, motors, solenoid valves, transformers and electronic circuits. They make it possible to reduce the space required for the equipment and various control circuits such as the control panel. There are detailed differences in the types of rated current available and the lineup includes multiple over current operation characteristics.
The lineup includes a wide variety of operation characteristics (instantaneous type, high-speed type, medium speed type, low speed type, medium speed type with inertial delay and low speed type with inertial delay), so it is possible to select the type suitable for the protection device.
Large type terminal covers have been prepared as an option for bare solderless terminals.
Installation in contact with other devices has been made possible when the terminal cover is attached.
It is a type for use on both AC and DC, so it can be used as it is for any circuit at or below 250 VAC or 65 VDC. Furthermore, when items are held in inventory, in addition to reducing the storage space, the management work is reduced and there is no mistaken arrangement for AC and DC.
The width per pole is extremely narrow and compact at just 17.5 mm per pole.
This makes a particularly large contribution to the reduction of the space required when the use is in large quantities.
Model | CP30-BA | CP30-HU | |||||||
---|---|---|---|---|---|---|---|---|---|
Number of poles | 1 | 2 | 3 | 1 | 2 | 3 | |||
Rated current (A) | 0.1 0.25 0.3 0.5 1 2 3 5 7 10 15 20 30 | 0.1 0.25 0.3 0.5 1 2 3 5 | |||||||
Rated short- circuit capacity (kA) |
UL 1077 CSA C22.2 No.235 |
Rated voltage |
AC (V) | 250 | 250 | ||||
DC (V) | 65 | 125 | - | 65 | 125 | - | |||
AC | 2.5kA at 250V | 2.5kA at 250V | 10kA at 250V | ||||||
DC | 2.5kA at 65V | 2.5kA at 125V | - | 10kA at 65V | 10kA at 125V | ||||
IEC 60934 EN 60934 GB 17701(*3) (Icn) |
Ui (V) | 250 | 250 | ||||||
AC | 2.5kA at 230V | 2.5kA at 230V 10kA at 120V |
10kA at 230V | ||||||
DC | 2.5kA at 60V | 2.5kA at 120V | - | 10kA at 65V | 10kA at 120V | ||||
IEC 60947-2 EN 60947-2 JIS C 8201-2-1 Ann.1 (Icu/Ics) |
Ui (V) | 250 | 250 | ||||||
AC | 2.5/2.5kA at 230V | 2.5/2.5kA at 230V 10/10kA at 120V |
10/10kA at 230V | ||||||
DC | 2.5/2.5kA at 120V | - | 10/10kA at 60V | 10/10kA at 120V | |||||
AC/DC common use | common | -(*1) | common | -(*1) | |||||
Mode of tripping | Instantaneous type(I); Medium type(M), (MD); Slow type(S), (SD); Fast type(F)(*2) |
Instantaneous type(I); Medium type(M), (MD); Slow type(S) |
|||||||
Body mounting method | IEC 35mm rail mounting | IEC 35mm rail mounting |
*(1) The 3-pole products are for AC use only.
(2) Contact us for operating characteristics other than those mentioned above.
(3) CP30-BA only.
Operates combined with the main circuit operating mechanism to electrically retrieve the ON/OFF status of protector.
Operates combined with the main circuit operating mechanism to electrically retrieve the tripping status of protector.
Remarks:
SHT can break the circuit instantaneously when the operating voltage is applied on SHT coil.
Classification | AC | DC | ||||||
---|---|---|---|---|---|---|---|---|
Voltage (V) |
Current (A) | Voltage (V) |
Current (A) | |||||
Resistive load | Inductive load | Resistive load | Inductive load | |||||
Ratings of items other than those shaded in Table 1 |
For general load |
Max. | (250) | (1) | (0.5) | 50 | 1 | 0.5 |
(250) | (1) | (0.5) | 50 | 1 | 0.5 | |||
Min. | 0.1A/15VAC | 0.1A/15VDC | ||||||
For minute load |
Max. | 125 | 0.5 | - | 30 | 0.5 | - | |
Min. | 1mA/24VDC, 2mA/12VDC, 5mA/6VDC | |||||||
Ratings of items shaded in Table 1 |
For general load |
Max. | (250) | (1) | (0.5) | (50) | (1) | (0.5) |
125 | 3 | (1) | 30 | (2), 0.5 | (1) | |||
Min. | 0.1A/15VAC | 0.1A/15VDC | ||||||
For minute load |
Max. | 125 | (0.5), 0.1 | - | 30 | (0.5), 0.1 | - | |
Min. | 1mA/24VDC, 2mA/12VDC, 5mA/6VDC |
Remark:
Ratings
Rated operating voltage (V) | Time rating | |
---|---|---|
100-200 | Compatible with 100 to 200 V AC and 100 V DC | 10 sec or less |
24-48 | Compatible with 24 to 48 V DC |
Coil resistance, resistance and impedance (at25°C)
Voltage (V) | Impedance for AC (Ω) | DC resistance for DC (Ω) |
---|---|---|
24-48 | - | 160 |
100-200 | 2400 | 2100 |
Remarks: