• twitter
  • facebook
  • mail

Products

Print Page

 

MELSEC iQ-F series

CC-Link IE field network

Model Master station function Remote,
slave function
Distance Compatible CPU module
FX5U FX5UC FX5UJ
FX5-CCLIEF
CC-Link IE field network
(Intelligent device station)
× 100 m *1

Up to 1 module
*1 *2

Up to 1 module

Up to 1 module

*1: Supported in version 1.030 or later.
*2: When connecting to FX5UC, FX5-CNV-IFC or FX5-C1PS-5V is required.

CC-Link

Model Master station function Remote,
slave function
Distance Compatible CPU module
FX5U FX5UC FX5UJ
FX5-CCL-MS
CC-Link system
master/intelligent
device module
1200 m *1
FX3U-16CCL-M *2
CC-Link
(Master station)
× 1200 m *3

Up to
1 module
*3

Up to
1 module
×
FX3U-64CCL
CC-Link
(Intelligent device station)
×

*1: FX5-CNV-IFC or FX5-C1PS-5V is necessary to connect to the FX5UC CPU module.

*2: When CC-Link master and AnyWire Bitty master or AnyWireASLINK master are used together, connect to the front stage (left side) of AnyWire Bitty master and AnyWireASLINK master. When used together, please refer to the FX3U-128ASL-M, FX3U-128BTY-M, and FX3U-16CCL-M user's manuals.

*3: When connecting to FX5U or FX5UC, FX5-CNV-BUS or FX5-CNV-BUSC is required. Select one according to the system configuration.

Ethernet

Model Data
transmission speed
Maximum
segment length
Supported protocol No. of connections
FX5U CPU module 100 / 10 Mbps 100 m
(The distance between hub and node)
・CC-Link IE field network Basic
・FTP Server
・SNTP client
・Web server (HTTP)
・Simple CPU communication function
・MELSOFT connection
・SLMP (3E frame)
・Socket communication
・Predefined protocol support
・MODBUS/TCP communication
Total of 8 connections*1*2
(Up to 8 external devices are accessible to one CPU module at a time.)
FX5UC CPU module
FX5UJ CPU module
FX5-ENET
Ethernet module

・CC-Link IE field network Basic
・Socket communication

Total of 32 connections*3
(Up to 32 external devices are accessible to one FX5-ENET at a time.)
FX5-ENET/IP
EtherNet/IP module

・EtherNet/IP
・Socket communication

Total of 32 connections
(Up to 32 external devices are accessible to one FX5-ENET/IP at a time.)

*1: The first device for MELSOFT connection is not included in the number of connections. (The second and the following devices are included.)

*2: The CC-Link IE field network Basic, FTP server, SNTP client, Web server and simple CPU communication function are not included in the number of connections.

*3: The CC-Link IE field network Basic are not included in the number of connections.

EtherNet/IP

Model Data
transmission speed
Maximum
segment length
Supported protocol Compatible CPU module
FX5U FX5UC FX5UJ
FX5-ENET/IP
EtherNet/IP module
100 / 10 Mbps 100 m
(The distance between hub and node)

・Class 1 communications
・Class 3 communications
・UCMM communications


Up to 1 module
*1

Up to 1 module

Up to 1 module

*1: When connecting to FX5UC, FX5-CNV-IFC or FX5-C1PS-5V is required.

PROFIBUS-DP

Model Transmission protocol Compatible CPU module
FX5U FX5UC FX5UJ
FX5-DP-M
PROFIBUS-DP Master module
PROFIBUS-DP
Up to 1 module
*1

Up to 1 module

Up to 1 module

*1: When connecting to FX5UC, FX5-CNV-IFC or FX5-C1PS-5V is required.

Sensor Solution

Model Transmission protocol Number of connected I/O points Compatible CPU module
FX5U FX5UC FX5UJ
FX5-ASL-M
AnyWireASLINK system master module
Dedicated protocol
(AnyWireASLINK)
448 points maximum *1*2*3
(input: maximum 256 points,
output: maximum 256 points)

Up to
1 module
*4

Up to
1 module

Up to
1 module
FX3U-128BTY-M *5
AnyWire Bitty series
master
Dedicated protocol
(AnyWire Bitty)
Up to 128 points *6

Up to
1 module
*6

Up to
1 module
×
FX3U-128ASL-M *5
AnyWireASLINK system master
Dedicated protocol
(AnyWireASLINK)

*1: The number of available remote I/O points per system varies depending on the number of I/O points of the extension devices.
*2: The maximum number of points that can be used differs depending on the version of the CPU module used.

*3: When connecting to the FX5UJ CPU module, the maximum is 216 points (input: maximum 192 points, output: maximum 192 points).

*4: FX5-CNV-IFC or FX5-C1PS-5V is necessary to connect to the FX5UC CPU module.

*5: When CC-Link master and AnyWire Bitty master or AnyWireASLINK master are used together, connect to the front stage (left side) of AnyWire Bitty master and AnyWireASLINK master. When used together, please refer to the FX3U-128ASL-M, FX3U-128BTY-M, and FX3U-16CCL-M user's manuals.

*6: When connecting to FX5U or FX5UC, FX5-CNV-BUS or FX5-CNV-BUSC is required. Select one according to the system configuration.

MODBUS communication

Model Communication interface Maximum transmission distance Generic Specifications Compatible CPU module
FX5U FX5UC FX5UJ
FX5-232-BD RS-232C 15 m ・Predefined protocol: RTU
・No. of connectable slaves: 1

Up to
1 modules
×
Up to
1 modules
FX5-232ADP
Up to
2 modules

Up to
2 modules

Up to
2 modules
FX5U CPU module RS-485 50 m ・Predefined protocol: RTU
・No. of connectable slaves: 32
- - -
FX5UC CPU module - - -
FX5-485-BD 50 m
Up to
1 module
×
Up to
1 module
FX5-485ADP 1200 m
Up to
2 module

Up to
2 module

Up to
2 module

Serial communication

Model Communication interface Maximum transmission distance Function type Compatible CPU module
FX5U FX5UC FX5UJ
FX5-232-BD RS-232C 15 m ・MELSOFT connection
・MELSEC Communication protocol (1C/3C/4C frames)
・Non-protocol communication
・Predefined protocol support

Up to
1 module
×
Up to
1 module
FX5-232ADP
Up to
2 module

Up to
2 module

Up to
2 module
FX5U CPU module RS-485 50 m ・MELSOFT Connection
・MELSEC Communication protocol (1C/3C/4C frames)
・Non-protocol communication
・Inverter communication
・N:N network
・Parallel link
・Predefined protocol support
- - -
FX5UC CPU module - - -
FX5-485-BD 50 m
Up to
1 module
×
Up to
1 module
FX5-485ADP 1200 m
Up to
2 module

Up to
2 module

Up to
2 module
FX5-422-BD-GOT RS-422 As per GOT specifications ・GOT connection
Up to
1 module
-
Up to
1 module