Lineup
Vacuum Circuit Breakers and Contactors
3.6/7.2/12/15/24kV Vacuum Circuit Breakers Type VPR
Introducing the all new VPR Series. This newly designed futuristic vacuum circuit breaker (VCB) offers high reliability and safety through leveraging leading-edge technologies and considering all aspects, from the environment to maintenance.
Ratings and Specifications
<3 /6-VPR Series> < 10-VPR Series> <15-VPR Series> <20-VPR Series>
High Reliability <10-VPR-D>
- Applying Mitsubishi Electric’s conventional vacuum valve technology as the basis, arc control technology and insulation design are leveraged to reduce size even further (i.e., 84% compared to conventional products) and increase reliability (E2 class).
 - The self-cooling VCB eliminates the need to mount a fan on the panel for a wide rated current range, from 600A to 3150A.
 - VCB has passed M2/E2/C2-class tests, ensuring high-quality standards compliant with IEC62271-100-2012.
 
*VI for 10-VPR-32D 1,250A
High Level of Safety <10-VPR-D>
Exposure of hot components in the main circuit are minimized in VCBs with rated currents up to 3150A. This increases safety through prevention of potential hazards such as short-circuiting caused by the intrusion of small animals.
Easy Installation and Simple Maintenance <10-VPR-D>
- Mechanical parts are coated with a long-life grease, helping to prevent oxidation and degradation, and lubricant-free bearings are used in the latch, thus extending the lubrication cycle for operational mechanisms from three years to six and reducing the time required for maintenance.
 - VCB removal and insert operation features a new external drawer operation method that uses a cam-slide mechanism in addition to the conventional lever-based removal/insert operation method, thereby making removal/insertion easier, quicker, and safer.
 - Enhanced options include an additional auxiliary switch and earthing switch.
 - VCBs with rated currents up to 3150A can be shipped with the panel using shipping clamps.
 - Can be easily exchanged with conventional model (10-VPR-C Series) mounting frame (same mounting hole positions, terminal/partition positions).
 
Eco-conscious Design <10-VPR-D>
- Does not use any of the six specified hazardous substances (mercury, cadmium, lead, hexavalent chromium, polybrominated biphenyls, and polybrominated diphenyl ethers; under regulated values stipulated by RoHS in force since FY2006). Another example is, use of a rust-proofing treatment for small parts, such as pins and screws, that is free of hexavalent chromium (i.e., a substance known to contaminate soil).
 - Recycling facilitated by displaying the names of materials used on major plastic parts.
 
Ratings and Specifications
| Type | 3-VPR-20D | 3-VPR-25D | 6-VPR-20D | 6-VPR-25D | 
|---|---|---|---|---|
| Rated voltage | 3.6kV | 7.2kV | ||
| Rated nominal current JEC | - | |||
| Rated nominal current IEC | 630A 1,250A  | 
|||
| Rated frequency | 50/60Hz | |||
| Rated breaking current | 20kA | 25kA | 20kA | 25kA | 
| Rated breaking time | 3 cycle | |||
| Compliant standards | - | |||
| IEC62271-100(2008) | ||||
| Type | 10-VPR-25D | 10-VPR-32D | 10-VPR-40D | 10-VPR-50C (D) | 
|---|---|---|---|---|
| Rated voltage(kV) | 12kV | |||
| Rated nominal current JEC | 600A 1,200A 1,600A 2,000A 2,500A 3,000A  | 
4,000A | ||
| Rated nominal current IEC | 630A 1,250A 2,000A 3,150A  | 
|||
| Rated frequency | 50/60Hz | |||
| Rated breaking current | 25kA | 31.5kA | 40kA | 50kA | 
| Rated breaking time | 3 cycle | |||
| Compliant standards | JEC-2300 (2010) | JEC-2300 (1998) | ||
| IEC62271-100 (2012) | IEC62271-100 (2008) | |||
| Type | 15-VPR-25D | 15-VPR-32D | 15-VPR-40D | 
|---|---|---|---|
| Rated voltage(kV) | 15kV | ||
| Rated nominal current JEC | - | ||
| Rated nominal current IEC | 630A 1,250A 1,600A 2,000A  | 
||
| Rated frequency(Hz) | 50/60Hz | ||
| Rated breaking current | 25kA | 31.5kA | 40kA | 
| Rated breaking time | 3 cycle | ||
| Compliant standards | --- | ||
| IEC62271-100 (2012) | |||
| Type | 20-VPR-16D | 20-VPR-25D | 20-VPR-25C | 
|---|---|---|---|
| Rated voltage(kV) | 24kV | ||
| Rated nominal current JEC | 600A 1,200A  | 
600A 1,200A  | 
600A 1,200A  | 
| Rated nominal current IEC | 630A 1,250A  | 
630A 1,250A 2,500A*  | 
630A 1,250A  | 
| Rated frequency | 50/60Hz | ||
| Rated breaking current | 16kA | 25kA | |
| Rated breaking time | 3 cycle | ||
| Compliant standards | - | JEC-2300 (1985) | |
| IEC62271-100 (2012) | IEC60056 (1987) | ||
- * The standard conforming to "20-VPR-25D type, 2500A" is "IEC62271-100 (2003)".